High Power Modular DC Power Supplies (SG Series)
Programmable Precision High Power DC Power Supply
Sorensen SG
Series Overview
The Sorensen SG Series (hereafter SG Series) represents the next generation of
high power programmable DC power supplies. The SG Series is designed for
exceptional load transient response, low noise and the highest power density in
the industry. With a full 15 kW available down to 20VDC output in a 3U package
the SG Series leads the industry in power density. The power density is
enhanced by a stylish front air intake allowing supplies to be stacked without
any required clearance between units.
At the heart of the SG series is a 5 kW power module. Depending on the output voltage, one to six modules can be configured in a single chassis to deliver 5 kW to 30 kW of power. Combinations of these chassis can then be easily paralleled to achieve power levels up to 150 kW. Paralleled units operate like one single supply providing total system current. Available in two control versions, the SGA has basic analog controls, while the SGI provides intelligent control features.
SGI: Advanced Intelligent Control
(Sorensen General purpose Intelligent) The SGI combines onboard intelligent
controls with the outstanding power electronics common to all SG family
supplies. These controls enable sophisticated sequencing, constant power mode
and save/recall of instrument settings. Looping of sequences makes the SGI
ideal for repetitive testing. An impressive vacuum fluorescent graphical
display in eight languages, context sensitive “soft” keys and front panel
keyboard simplify programming of the SGI.
SGA:
Outstanding Value - Analog Control
(Sorensen General purpose Analog) The SGA, with its industry leading performance,
is available for customers requiring simple front panel analog controls or
external control. With the same high performance power electronics as the SGI,
the SGA provides essential features like 10- turn potentiometers for setting
voltage and current, 3 ½ digit LED readout plus front panel over-voltage
protection (OVP) preview/adjustment and reset.
SGI / SGA Comparison Chart
Feature | SGA | SGI |
Modular Design | • | • |
Fast Load Transient | • | • |
Parallelable | • | • |
Analog & Digital Summing | Optional | • |
Direct Front Panel V/1 Control | • | • |
3½ Digit LED Readout | • | |
Graphics Display | • | |
Sequencing | • | |
Save / Recall Setups | • | |
System Power Readouts | • | |
Constant Power Mode | • | |
IEEE-488.2/RS-232C | Optional | RS-232C Std |
LXI Class C Ethernet/ RS-232 | Optional | RS-232C Std, Ethernet Optional |
Front Panel Dust Filter | Optional (3U unit only) | Optional (3U unit only) |
Applications | |
Burn-In | Compliance Testing |
Materials Research | Process Control |
Product Validation | Automotive Electronics |
Rackmount ATE Systems | Battery Charging |
See the SFA product page for very high current slew rate and low stored energy applications. |
Sorensen SG Series Specifications
Common | |
Remote Sense | Terminals are provided to sense output voltage at point of load. Maximum line drop 5% of rated voltage per line for 40-100V models, line drop 1V of rated voltage per line for 10-20V models, 1.5V for 30V models, 2% of rated voltage per line for models 160V and greater. (Greater line drop is allowed, but output regulation specifications no longer apply). |
Parallel Operation | Up to 5 units may be paralleled for additional current within the power supply single-unit specifications, with exception of the DC output current set accuracy. Additional paralleled SG units will add 0.3% inaccuracy per unit. To parallel more than 5 units, contact factory. |
Series Operation | Up to 2 units (see Output Float Voltage) |
Input | |
Nominal
Voltage | 208/230
VAC (operating range 187 - 253 VAC) |
Frequency | 47 – 63Hz , 400Hz ( 400Hz @ 208VAC, for 6U units is optional modification and does not carry CE, UL or CSA markings ) |
Power Factor | >0.9
typical for 10V - 30V, 50V, 1000V and other models with optional “PF”
modification. |
Protection | ½ cycle ride-though , typical, on all three phases, 3 cycle ride through on single phase; missing phase shutdown ( 800V model 6.4 msec on all 3 phases ) |
Programming & Read-back Specifications ( with sense wires used ) | ||||||||
| Programming | Read-Back / Monitoring |
| |||||
Accuracy | Resolution | Accuracy | Resolution | |||||
Front panel Display | SGA: +/- (0.5%fs + 1 digit) SGI (40-1000V) +/- 0.1% of voltage at full scale SGI (40-1000V) +/- 0.4% of current at full scale | SGA: 3.5 digits SGI: 4.0 digits | SGA: +/- (0.5%fs + 1 digit) SGI, Voltage: +/- 0.1% of full scale SGI, Current: +/- 0.4% of full scale | SGA: 3.5 digits SGI: 4.0 digits | Knob control & Display read-back | |||
SGI (10-30V) 0.1% of set point +0.1% of voltage rating SGI (10-30V) 0.1% of set point +0.4% of current rating | SGI (10-30V) 0.1% of actual +0.15% voltage rating | |||||||
Remote Analog Interface | Voltage +/-0.25% of full scale Current (40-1000V) 0.8% of full scale , (10-30V) 1.0% of full scale | N/A | (40-1000V) +/-1.0% of full scale | N/A | 25-pin D-sub connector (0~5 V or 0~10 V) | |||
(10-30V) +/-0.5% of full scale | ||||||||
Remote Digital Interface | Voltage: +/- 0.1% of full scale, Current: +/- 0.4% of full scale | +/-0.002% of full scale | Voltage:
+/- 0.1% of full scale | +/-0.002% of full scale | RS-232C (Standard on SGI), Optional IEEE-488.2 and Optional LXI Compliant 10/100 base-T Ethernet (see Options) | |||
OVP | +/- 1% of full scale | +/-0.002% of full scale |
|
| Programming range: 5-110% Configured from front panel, remote analog or via optional digital inputs | |||
User I/O | Disconnect & Polarity-reversal relay control ( Only available with Ethernet Option ) | Digital 10-pin Molex type connector Chart Below | ||||||
Software | IVI & CVI drivers available under DOWNLOADS at: www.ProgrammablePower.com | |||||||
Physical | ||||||||
| 3U Models (10V-30V) | 3U Models (40V-1000V) | 6U Models (60V-600V) | |||||
Width | 19.00 in (48.3 cm) | 19.00 in (48.3 cm) | 19.00 in (48.3 cm) | |||||
Depth | 28.09 in (71.35 cm) | 26.4 in (67.1 cm) | 27.06 in (68.8 cm) | |||||
Height | 5.25 in (13.3 cm) | 5.25 in (13.3 cm) | 10.5 in (26.7 cm) | |||||
Weight | (4kW, 10V 15V) ≈<65 lbs
(29 kg) | (5kW) ≈ ≤60 lbs (27 kg) | (20kW) ≈ ≤140 lbs (64 kg) | |||||
Shipping Weight | Contact factory for more product & shipping weights | |||||||
Output | ||||
Ripple & Noise (Voltage Mode, Typical) | See Output: Voltage & Current Ranges Chart above. Ripple and noise specified at full load, nominal AC input. Noise measured with 6ft. cable, 1μf at load | |||
Output Rise Time (40-800V) | ≈< 100 ms 5-95% of full scale typical - resistive load (Contact factory for model specific slew rates) | |||
Output
Rise Time | Rise Time, ms, MAX | Condition | ||
10 | Measured from 10% to 90% of the output voltage change - resistive load, typical | |||
Output
Voltage Fall Time | Fall Time, MS MAX | Condition | ||
No Load 1 | 100% CC Load 10 | 100% CR Load 10 | Measured from 90% to 10% of the output voltage change. - resistive load, typical | |
Output
Current Rise Time | Rise Time, ms, MAX | Condition | ||
20 | Measured from 10% to 90% of the output current change - resistive load, typical | |||
Output
Current Fall Time | Rise Time, ms, MAX | Condition | ||
10 | Measured from 90% to 10% of the output current change - resistive load, typical | |||
Line Regulation (with sense wires used) | (±10%
of nominal AC input, constant load) | |||
Load Regulation (with sense wires used) | (no load to full load, nominal AC input) | |||
Load Transient Response | Recovers within 1ms to +/-0.75% of full-scale of steadystate output for a 50% to 100% or 100% to 50% load change | |||
Efficiency | 87% typical at nominal line and max load | |||
Stability | ±0.05% of set point after 30 minute warm-up and over 8 hours at fixed line, load and temperature, typical | |||
Temperature Coefficient | 0.02%/ C of maximum output voltage rating
for voltage set point, typical | |||
Output Float Voltage | Negative
terminal within +/- 300 V of chassis potential. | |||
Environmental | |
Operating Temperature | 0 to 50º C |
Storage Temperature | -25º C to 65º C |
Humidity Range | Relative humidity up to 95% non-condensing, 0º C – 50º C |
Altitude | Operating full power available up to 5,000 ft. (~1,500 m), derate 10% of full power for every 1,000 feet higher; non-operating to 40,000 ft. (~12,000 m) |
Cooling | Front and side air inlet, rear exhaust. Temperature controlled, variable speed fans. Units may be stacked without spacing. |
Regulatory | Certified to UL/CSA 61010 and IEC/EN
61010-1 by a NRTL, CE Compliant, Semi-F47 Compliant. |
Front Panel Dust Filter | 30
PPI (Pores Per Inch) - must ensure adequate airflow and / or derate max.
temperature. |
Output: Voltage and Current Ranges
3U | 6U | Ripple & Noise | ||||||
Power | 4/5 kW | 8/10 kW | 12/15 kW | 16/20 kW | 20/25 kW | 24/30 kW | rms (20Hz-00kHz) | p-p (20Hz-20MHz) |
Voltage | Current | Current | ||||||
10 | 400 | 800 | 1200 | 1600* | 2000* | 2400* | 20mV | 50mV |
15 | 267 | 534 | 801 | 1068* | 1335* | 1602* | 20mV | 50mV |
20 | 250 | 500 | 750 | 1000* | 1250* | 1500* | 20mV | 60mV |
30 | 167 | 334 | 501 | 668* | 835* | 1002* | 20mV | 60mV |
40 | 125 | 250 | 375 | 500* | 625* | 750* | 20mV | 75mV |
50 | 100 | 200 | 300 | 400* | 500* | 600* | 20mV | 75mV |
60 | 83 | 167 | 250 | 333 | 417 | 500 | 20mV | 75mV |
80 | 63 | 125 | 188 | 250 | 313 | 375 | 20mV | 100mV |
100 | 50 | 100 | 150 | 200 | 250 | 300 | 20mV | 100mV |
160 | 31 | 63 | 94 | 125 | 156 | 188 | 25mV | 150mV |
200 | 25 | 50 | 75 | 100 | 125 | 150 | 25mV | 175mV |
250 | 20 | 40 | 60 | 80 | 100 | 120 | 30mV | 200mV |
300 | 17 | 33 | 50 | 67 | 83 | 100 | 30mV | 200mV |
330 | 15 | 30 | 45 | 61 | 76 | 91 | 30mV | 200mV |
400 | 12 | 25 | 38 | 50 | 63 | 75 | 30mV | 300mV |
500 | 10 | 20 | 30 | 40 | 50 | 60 | 50mV | 350mV |
600 | 8 | 17 | 25 | 33 | 42 | 50 | 60mV | 350mV |
800 | 6.2 | 12.5 | 18.7 | 25* | 31.2* | 37.5* | 80mV | 500mV |
1000 | 5 | 10 | 15 | 20* | 25* | 30* | 100 mV | 650 mV |
* By way of paralleling 5kW, 10kW & 15kW supplies
Analog User I/O Pinouts | |||
1 | Isolated Remote ON/OFF | 14 | Isolated TTL/CMOS ON/OFF Control |
2 | Isolated Circuit Return | 15 | Remote Voltage Programming |
3 | Remote Overvoltage Set | 16 | Remote Current Programming |
4 | Voltage Return for Pins 9, 15, or 21 | 17 | Fault State |
5 | Remote ON/OFF | 18 | Shutdown Fault |
6 | Circuit Common | 19 | Output Voltage Monitor |
7 | Output Current Monitor | 20 | Voltage Return for Pins 9, 15, or 21 |
8 | Local Voltage Control Monitor | 21 | Voltage Control Resistance |
9 | Remote Voltage Programming | 22 | Current Control Resistance |
10 | Remote Current Programming | 23 | Current Return for Pins 10, 16, or 22 |
11 | Local Current Control Monitor | 24 | Circuit Common |
12 | Not Used | 25 | Current Return for Pins 10, 16, or 22 |
13 | Not Used |
|
Digital User I/O Pinouts ( Ethernet Option Only ) | |
1 | Fold Back Monitor |
2 | Direct Shutdown |
3 | Fault Indication |
4 | Trigger Out |
5 | Common |
6 | Polarity output reversal signal |
7 | Isolation relays relay open signal |
8 | Sense relays open signal |
9 | Common |
10 | Trigger in |
Control Options
A: Analog
I: Intelligent
Input Options
C: Input Voltage 187 / 242VAC, 3 Phase
D: Input Voltage 342 / 440VAC, 3 Phase
E: Input Voltage 396 / 528VAC, 3 Phase
Remote Control Options
0A: No Option
1A: IEEE-488.2 + RS-232C (Note: SGI comes standard with RS-232C)
1C: Ethernet + RS-232C
1D: Isolated Analog Control
1E: Shaft Locks (SGA series only)
2A: Combined Options 1A+1D
2C: Combined Options 1A+1E (SGA Only)
2G: Combined Options 1C+1D
2H: Combined Options 1C+1E (SGA Only)
2J: Combined Options 1D+1E (SGA Only)
3C: Combined Options 1A+1D+1E (SGA Only)
3G: Combined Options 1C+1D+1E (SGA Only)
Process Options
AA: No option
AB: Certificate of Calibration to ANSI / NCSL Z540-1 (includes Test Data)
Modifications
AJ: Front panel dust filter - factory installed - 3U unit only
CV: 400Hz AC input @ 208 VAC ( does not carry CE, CSA or UL marks ) ( 6U only ) STD on 3U
PF: Passive power factor correction to 0.9 (Only applicable to 40V, 60V to 800V. Included in 10V-30V, 50V and 1000V.)
Accessories
890-453-03: Paralleling Cable (for up to 5 units, requires one cable per unit placed in parallel)
K550212-01: 3U Rack Slides (for 5kW, 10kW and 15kW models)
K550213-01: 6U Rack Slides (for 20kW, 25kW and 30kW models)
K550532-01: Front panel dust filter - field installation kit - 3U unit only
5551082-01: Optional AC input cover kit - 3U unit only